Solar BOS

Solar ACDB selection guide

Match the inverter's AC output to the ACDB incomer rating, then send us the SLD for a quotation.

Selection guide

Inverter AC rating to ACDB incomer breaker

Inverter AC outputSystemRated AC currentIncomer breaker (125% of current, next standard size)
1 kW1-phase 230 V4.3 A6 A
2 kW1-phase 230 V8.7 A16 A
3 kW1-phase 230 V13.0 A20 A
5 kW1-phase 230 V21.7 A32 A
5 kW3-phase 415 V7.0 A10 A
8 kW3-phase 415 V11.1 A16 A
10 kW3-phase 415 V13.9 A20 A
15 kW3-phase 415 V20.9 A32 A
20 kW3-phase 415 V27.8 A40 A
25 kW3-phase 415 V34.8 A50 A
30 kW3-phase 415 V41.7 A63 A
33 kW3-phase 415 V45.9 A63 A
40 kW3-phase 415 V55.6 A80 A
50 kW3-phase 415 V69.6 A100 A
60 kW3-phase 415 V83.5 A125 A
80 kW3-phase 415 V111.3 A160 A
100 kW3-phase 415 V139.1 A200 A
125 kW3-phase 415 V173.9 A250 A

Guide only, at unity power factor. Final breaker, cable, SPD and metering selection follows the approved design, site fault level and the inverter manufacturer's datasheet.