Solar ACDB selection guide
Match the inverter's AC output to the ACDB incomer rating, then send us the SLD for a quotation.
Selection guide
Inverter AC rating to ACDB incomer breaker
| Inverter AC output | System | Rated AC current | Incomer breaker (125% of current, next standard size) |
|---|---|---|---|
| 1 kW | 1-phase 230 V | 4.3 A | 6 A |
| 2 kW | 1-phase 230 V | 8.7 A | 16 A |
| 3 kW | 1-phase 230 V | 13.0 A | 20 A |
| 5 kW | 1-phase 230 V | 21.7 A | 32 A |
| 5 kW | 3-phase 415 V | 7.0 A | 10 A |
| 8 kW | 3-phase 415 V | 11.1 A | 16 A |
| 10 kW | 3-phase 415 V | 13.9 A | 20 A |
| 15 kW | 3-phase 415 V | 20.9 A | 32 A |
| 20 kW | 3-phase 415 V | 27.8 A | 40 A |
| 25 kW | 3-phase 415 V | 34.8 A | 50 A |
| 30 kW | 3-phase 415 V | 41.7 A | 63 A |
| 33 kW | 3-phase 415 V | 45.9 A | 63 A |
| 40 kW | 3-phase 415 V | 55.6 A | 80 A |
| 50 kW | 3-phase 415 V | 69.6 A | 100 A |
| 60 kW | 3-phase 415 V | 83.5 A | 125 A |
| 80 kW | 3-phase 415 V | 111.3 A | 160 A |
| 100 kW | 3-phase 415 V | 139.1 A | 200 A |
| 125 kW | 3-phase 415 V | 173.9 A | 250 A |
Guide only, at unity power factor. Final breaker, cable, SPD and metering selection follows the approved design, site fault level and the inverter manufacturer's datasheet.